Commercial
10Kw - 12.5Kw

ABB three-phase inverter designed for commercial usage


ABB three-phase inverter is highly unique in its ability to control the performance of the solar PV panels, especially during periods of variable weather conditions.

Two independent MPPTs and efficiency ratings up to 97.8%

This transformerless device has two independent MPPTs and efficiency ratings of up to 97.8%. The wide input voltage range makes the inverter suitable to low power installations with reduced string size. It is available with an optional fully-integrated DC switch, fuse and remote controlled DC disconnect function. The unit is free of electrolytic capacitors, leading to a longer product lifetime.

The high speed and precise Maximum Power Point Tracking (MPPT) algorithm provides real-time power tracking and improved energy harvesting.


 Flat efficiency curves ensure high efficiency at all output levels ensuring consistent and stable performance across the entire input voltage and output power range.


The wide input voltage range makes the inverter suitable for low power installations with reduced string size.



Highlights

  • True three-phase bridge topology for DC/AC output converter
  • Transformerless topology
  • Each inverter is set on specific grid codes which can be selected in the field
  • Wide input range
  • Dual input section with independent MPPT allows optimal energy harvesting from two sub-arrays oriented in different directions
  • Integrated DC disconnect switch in compliance with international standards (-S and -FS versions)
  • Natural convection cooling for maximum reliability
  • Outdoor enclosure for unrestricted use under any environmental conditions
  • RS-485 communication interface (for connection to laptop or datalogger)

 

Type code PVI-10-TL-OUTD   PVI-12.5-TL-OUTD
Input side  
Absolute maximum DC input voltage (Vmax,abs) 900 V
Start-up DC input voltage (Vstart) 360 V (adj. 250...500 V)
Operating DC input voltage range (Vdcmin...Vdcmax) 0.7 x Vstart...850 V (min 200 V)
Rated DC input voltage (Vdcr) 580 V
Rated DC input power (Pdcr) 10300 W   12800 W
Number of independent MPPT 2
Maximum DC input power for each MPPT (P MPPTmax) 6500w   8000w
DC input voltage range with parallel configuration of MPPT at Pacr 300...750 V   360...750 V
DC power limitation with parallel configuration of MPPT Linear derating from max to null [750 V≤VMPPT≤850 V]
DC power limitation for each MPPT with independent configuration of MPPT at Pacr, max unbalance example 6500 W [380 V≤VMPPT≤750 V] the other channel: Pdcr-6500 W [225 V≤VMPPT≤750 V]   8000 W [445 V≤VMPPT≤750 V] the other channel: Pdcr-8000 W [270 V≤VMPPT≤750 V]
Maximum DC input current (I dcmax) / for each MPPT (I MPPTmax) 34.0 A / 17.0 A 36.0 A / 18.0 A
Maximum input short circuit current for each MPPT 22.0 A
Number of DC input pairs for each MPPT 2
DC connection type PV quick fit connector
  
Input protection
Reverse polarity protection Yes, from limited current source
Input over voltage protection for each MPPT - varistor Yes
Photovoltaic array isolation control According to local standard
DC switch rating for each MPPT (version with DC switch 25 A / 1000 V
Fuse Rating (version) 15A / 1000V
Output side
AC grid connection type Three-phase 3W+PE or 4W+PE
Rated AC power (Pacr @cosφ=1) 10000 W   12500 W
Maximum AC output power (Pacmax @cosφ=1) 11000 W
  13800 W
Maximum apparent power (S max) 11500 VA   13800 VA
Rated AC grid voltage (Vac,r) 400 V
AC voltage range 320...480 V
Maximum AC output current (I ac,max) 16.6 A   20.0 A
Contributory fault current 19.0 A   22.0 A
Rated output frequency (fr) 50 Hz / 60 Hz
Output frequency range (fmin...fmax) 47...53 Hz / 57…63 Hz
Nominal power factor and adjustable range
> 0.995, adj. ± 0.9 with Pacr=10.0 kW,± 0.8 with max 11.5 kVA  
  > 0.995, adj. ± 0.9 with Pacr=12.5 kW,± 0.8 with max 13.8 kVA 
Total current harmonic distortion < 2%
AC connection type Screw terminal block, cable gland M40
Output protection
Anti-islanding protection According to local standard
Maximum external AC overcurrent protection   25.0 A  
Output overvoltage protection - varistor 3 + gas arrester
Operating performance
Maximum efficiency (ηmax) 97.80%
Weighted efficiency (EURO/CEC) 97.1% / -
97.2%
Feed in power threshold 30.0 W
Night consumption < 1.0 W
Communication
Wired local monitoring PVI-USB-RS232_485 (opt.)
Remote monitoring VSN300 Wifi Logger Card (opt.), VSN700 Data Logger (opt.)
Wireless local monitoring VSN300 Wifi Logger Card (opt.)
User interface 16 characters x 2 lines LCD display
Environmental
Ambient temperature range -25...+60°C /-13...140°F with derating above 55°C/122°F   -25...+60°C /-13...140°F with derating above 50°C/122°F
Relative humidity 0...100% condensing
Sound pressure level, typical 50 dBA @ 1 m
Maximum operating altitude without derating 2000 m / 6560 ft
Physical
Environmental protection rating IP65
Cooling Natural
Dimension (H x W x D) 716 mm x 455 mm x 224 mm / 28.2” x 25.4” x 8.8”
Weight 41.0 kg / 90.4 lbs
Mounting system Wall bracket
Safety
Isolation level Transformerless
Marking CE (50 Hz only), RCM
Safety and EMC standard EN 50178, IEC/EN 62109-1, IEC/EN 62109-2, AS/NZS 3100, EN 61000-6-1, EN 61000-6-3,
Grid standard (check your sales channel for availability) EN 61000-3-11, EN 61000-3-12, CEI 0-21, DIN V VDE V 0126-1-1, VDE-AR-N 4105, G83/2, G59/3, EN 50438 (not for all national appendices), RD 1699, RD 413, ITC-BT-40, AS 4777, IEC 61727, IEC 62116
Available products variants
Standard PVI-10.0-TL-OUTD   PVI-12.5-TL-OUTD
With DC switch PVI-10.0-TL-OUTD-S   PVI-12.5-TL-OUTD-S

Call us today

1 300 764 427

info@advancedallenergy.com.au

Visit Our Showroom

977 Port Road, Cheltenham,
S.A. 5014

MON: 9am - 5pm
TUE: 9am - 5pm
WED: 9am - 5pm
THU: 9am - 5pm
FRI: 9am - 5pm
SAT: by appointment
SUN: by appointment

$5000 Solar or Battery Storage Rebates
Solar or Battery Storage Rebates are still available, Call Advanced All Energy
TODAY 1300 764 427 to find out more.